Hvac School - For Techs, By Techs
Electrical Myths - Hard Starts Reduce Start Current - Short #156
- Author: Vários
- Narrator: Vários
- Publisher: Podcast
- Duration: 0:15:41
- More information
Informações:
Synopsis
In this short podcast, Bryan busts the myth that hard starts reduce the start current on the run winding of a compressor. A single-phase motor’s main winding is the run winding; it has a lower resistance and a higher current than the auxiliary winding, also known as the start winding. Hard start kits are often used on HVAC systems with single-phase compressors (which usually have PSC motors). These kits usually consist of a start capacitor and a potential relay, which takes the start capacitor out of the circuit. We don’t typically use hard starts on three-phase motors or ECMs. Single-phase compressors often have to start under a big load, especially in long-line applications (at the manufacturer’s recommendation) or if the compressor simply has a hard time starting. In cases where you have a voltage drop or low voltage, particularly due to long branch circuits, you may also use a hard start kit. However, they do NOT reduce the starting current or “save” compressors. Hard starts reduce the time-averaged star