Hvac School - For Techs, By Techs
Total Heat of Rejection - Short #152
- Author: Vários
- Narrator: Vários
- Publisher: Podcast
- Duration: 0:10:06
- More information
Informações:
Synopsis
In this short podcast, Bryan talks about THOR, total heat of rejection. He explains what it is and why we should care about it when working on HVAC/R systems. THOR is another aspect of pressure-enthalpy calculations, along with net refrigeration effect (NRE) and total heat of compression. When we talk about system capacity, we’re often referring to heat absorbed in the evaporator coil (NRE). Heating is on the opposite side of the coin; when we bring heat into a home, we care more about how much heat is rejected than absorbed. That’s where THOR comes in. More heat is rejected at the condenser than absorbed in the evaporator. The total heat content increases due to additional heat being absorbed in the suction line. Compressors also have motors that aren’t 100% efficient, so a bit of inefficiency also adds a small amount of heat to the refrigerant (in a system operating normally). All of that heat adds up to the total heat of rejection (THOR). Even though a higher total heat of rejection is desirable when we