Synopsis

In this short podcast episode, Bryan talks about ERV and HRV technologies, including their appropriate applications and limitations. HRVs are heat recovery ventilators (not to be confused with heat recovery units or HRUs), and ERVs are energy recovery ventilators. The main difference between these two lies in the type of heat they move; HRVs only move sensible BTUs, whereas ERVs move sensible and latent BTUs.  As you bring air in from outside, you’re discharging roughly the same amount of air (though modern technologies allow you to manipulate the pressure a bit more). The goal of the HRV or ERV is to recover some energy from the air exiting the structure and incorporate it into the incoming airstream. The airstreams cross over each other, and there is heat transfer but not air mixing. (ERVs also allow for the exchange of moisture.) Two fans drive the direction of energy flow, and a mesh or a porous desiccant medium facilitates the interaction between the airstreams. You will get some energy savings with an H