Q&A - Drain Traps & Static - Short #209

Informações:

Synopsis

In this short Q&A podcast episode, Bryan answers a question about drain traps and static pressure. This question was sent by Stephen with The Comfort Squad when he noticed an uptick in nuisance calls on retrofit systems that kept having their secondary drain pans filled. In negatively pressurized systems (i.e., straight-cool or heat pump units, not gas furnaces), air can pull water back into the drain line. The evaporator coil is under negative pressure because the blower is on top of the evaporator coil. The rule of thumb for trap depth is that it should be greater than or equal to twice the return static pressure (which is why a 1" deep trap is typical for systems with 0.5" return static pressure). However, return static can have some variation, and it's also not a great idea to use the TESP for this measurement because the return static could be greater than the supply. It makes most sense to account for the highest possible return static you will see. 1" is only sufficient if 0.5" return static pressu