Hvac School - For Techs, By Techs
Duct Smoke Detector Facts and Wiring - Short #203
- Author: Vários
- Narrator: Vários
- Publisher: Podcast
- Duration: 0:12:44
- More information
Informações:
Synopsis
In this short podcast, Bryan answers a listener-submitted question about duct smoke detector facts and wiring. He focuses on Honeywell duct smoke detectors (namely the D4120W), but there are some general best practices that can be applied to most duct smoke detectors. The power supply may be 24v or 120v AC or DC and may have multiple inputs. You should not break that constant power source. There are also fan shutdown contacts, which may be normally open (alarm condition) or normally closed (non-alarm condition). Supervisory contacts open to indicate a trouble condition to the panel when something in the circuit isn't working properly (NOT an alarm condition). There is often a resistor at the end of the loop, and the alarm panel recognizes a specific resistance. Alarm initiation contacts close and create a shorted condition when there is an alarm condition (the supervisory contacts open if there is a trouble condition). Smoke detectors in the ducts are different from the ones on ceilings; they usually shut do