Hvac School - For Techs, By Techs

Solving & Preventing Oil Issues in Rack Refrigeration

Informações:

Synopsis

In this HVAC podcast episode, hosts Bryan Orr and Matthew Taylor (refrigeration leader and trainer at Kalos Services) discuss oil management and considerations in supermarket refrigeration systems, with a focus on solving & preventing oil issues. They talk about the importance of stable system operation and how oil flows through both active and passive systems in these larger built-up racks. Matthew explains that in a rack system, oil is actively separated and returned to the compressors through a dedicated system. However, not all oil gets captured this way, so the passive system of oil returning through the refrigeration cycle still occurs. Problems can arise in either system, leading to compressors locking out. Matthew stresses properly setting and regulating EPR valves to minimize load fluctuations that impact system stability. Common issues covered include clogged oil separators, misadjusted or damaged oil controls, changes in suction pressure affecting oil flow, the impact of floating suction pressu