Hvac School - For Techs, By Techs

ROT Can Cause Duct Issues - Short #160

Informações:

Synopsis

In this short podcast, Bryan explains how rules of thumb (ROT) can cause duct issues. He talks about the role of friction rate in duct design as well as its intent and limitations. Friction rate is a value located on duct calculation tools, including Ductulators. We use friction rate to predict the operating static pressure of the system, but it is often misapplied when people design their ductwork around rules of thumb. The friction rate is expressed in inches of water column ("WC), which we also use to measure static pressure. However, the operational static pressure and friction rate are NOT the same things. Ductulators provide information about friction rate based on 100 feet of straight ductwork in the size selected, which we almost never see in the field; fittings and turns add effective length (EL), so the total effective length (TEL) is often more than 100 feet. When duct designers apply rules of thumb, like a 0.1" friction rate, and apply it to the CFM, they don't consider the actual length of the du